____________________________________________________________________
Standard functions and function blocks normally cannot be removed
from the ISaGRAF workbench menus, as they are considered in ISaGRAF
V3.xx as internal parts of the ISaGRAF target. It follows exactly
the same principle as the one applied to data types and languages.
Example: if a target does not support REAL data type, both variable
declaration and concerned function blocks cannot be removed from the
workbench environment.
It is technically possible to hide some function blocks in the
editor menus. Standard blocks are defined in the ASCII file
"\ISAWIN\EXE\ISA.LIB'. Each block declaration is a group of
lines. The first line begins with '{' ; the last line is '}'. To
inhibit the declaration of one block, just insert a ';' character
at the beginning of each concerned line.
WARNING: This corresponds to a specific customization (even if very
short), and must be clearly registered in ISaGRAF with corresponding end
user identification, as it is not a standard feature of the product,
and creates an 'abnormal' situation for support. Such
customization is normally not supported by ISaGRAF releases.
See also FAQ:
Wbstdlib.where standard F and FB are defined in the ISaGRAF Workbench
in Workbench directory